Key Features
- Rated power and overload: Rated power: 90.00 kW | 100.00 hp (LO); 75.00 kW | 75.00 hp (HO). The collected description states 150% overload for 3 s.
- Input and output ratings: Input: 380 … 480 V +10 % -20 %, 47 … 63 Hz, 3 AC. Output: 3 AC, rated voltage 400V IEC | 480V NEC 1).
- Communication and safety: Communication: PROFINET, EtherNet/IP. Safe Torque Off is integrated.
- I/O configuration: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output.
- Control techniques: Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
- Mechanical configuration and protection: Frame size: FSF. Dimensions: 305 mm width and 357 mm depth. Degree of protection: IP20 / UL open type. Net weight: 57.50 kg (126.77 lb).
Technical Summary
| Product | Siemens SINAMICS G120C compact converter |
|---|---|
| Order number | 6SL3210-1KE31-7UF1 |
| Rated power (LO) | 90.00 kW | 100.00 hp |
| Rated power (HO) | 75.00 kW | 75.00 hp |
| Input | 380 … 480 V +10 % -20 %, 3 AC, 47 … 63 Hz |
| Communication | PROFINET, EtherNet/IP |
| Safety function | Safe Torque Off integrated |
| Output frequency for vector control | 0 … 240 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Frame size | FSF |
| Degree of protection | IP20 / UL open type |
Frequently Asked Questions
What is the rated power of Siemens 6SL3210-1KE31-7UF1?
Rated power is 90.00 kW | 100.00 hp (LO) or 75.00 kW | 75.00 hp (HO).
Which communication interfaces are supported?
Communication is PROFINET and EtherNet/IP.
What I/O does this converter have?
It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output.
What are the frame size and protection rating?
Frame size is FSF, and the degree of protection is IP20 / UL open type.