Product information
Overview
Key Features
- Rated power and overload: Rated power: 1.50 kW | 2.00 hp (LO) or 1.10 kW | 1.50 hp (HO). Low overload: 150% for 3s, 110% for 57s, 100% for 240s. High overload: 200% for 3s, 150% for 57s, 100% for 240s.
- Input and output ratings: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC, maximum output current 6.20 A.
- Control and communication: Control options include V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Communication: PROFIBUS DP.
- I/O configuration: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 digital output as relay changeover contact, 1 digital output as transistor, 1 differential analog/digital input and 1 non-isolated analog output.
- Connections and protection: Line-side, motor-end and DC-link connections use plug-in screw terminals. Protection: IP20 / UL open type. Integrated filter: Class A.
- Mechanical data: Frame size: FSAA. Dimensions: 73 mm width and 155 mm depth. Net weight: 1.40 kg (3.09 lb).
Technical Summary
| Product | 6SL3210-1KE14-3AP2 |
|---|---|
| Product lifecycle | Active Product |
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power (LO) | 1.50 kW | 2.00 hp |
| Rated power (HO) | 1.10 kW | 1.50 hp |
| Communication | PROFIBUS DP |
| Protection | IP20 / UL open type |
| Frame size | FSAA |
Frequently Asked Questions
What is the rated power of Siemens 6SL3210-1KE14-3AP2?
It has 1.50 kW | 2.00 hp rated power under low overload and 1.10 kW | 1.50 hp under high overload.
Which communication interface does this SINAMICS G120C drive have?
It has a PROFIBUS DP communication interface.
What I/O is included?
It has 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input and 1 non-isolated analog output.
What are the connection and protection details?
Line-side, motor-end and DC-link connections use plug-in screw terminals. Protection is IP20 / UL open type.
How can I request a quotation for this configuration?
Send the required quantity, destination and requested date for an MRO or project quotation.