ET 200SP Remote I/O Parts

6ES7134-6GB00-0BA1

Product details

Product Code
6ES7134-6GB00-0BA1
Dimensions
7.9 × 6.8 × 2.4 cm
Weight
0.039 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • Analog input capacity: 2 analog inputs, both supporting current measurement.
  • Input ranges and resolution: Supports 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA input ranges, with up to 16 bit resolution including sign.
  • Supply and encoder output: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Encoder supply output is 50 mA max. total for both channels in two-wire mode.
  • Conversion performance: Minimum cycle time for all channels is 500 μs. Conversion time is 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, or 500 μs without filter.
  • Diagnostics and protection: Provides supply-voltage monitoring, wire-break diagnosis at 4 mA to 20 mA, encoder-supply short-circuit diagnosis, group error, overflow/underflow, and reverse-polarity protection.
  • Installation and dimensions: Suitable for BU type A0, A1 and 1-wire, 2-wire, or 4-wire connections. Dimensions are 15 mm wide, 73 mm high, and 58 mm deep.

Technical Summary

Product type designation AI 2xI 2-/4-wire ST
Analog inputs 2
Input ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Resolution with overrange 16 bit including sign
Rated supply voltage 24 V DC
Permissible supply voltage range 19.2 V to 28.8 V DC
Cycle time, all channels, min. 500 μs
BaseUnits BU type A0, A1
Conversion time 50 ms @ 60 Hz; 60 ms @ 50 Hz; 180 ms @ 16.6 Hz; 500 μs without filter
Diagnostics Supply voltage, wire break at 4 mA to 20 mA, encoder-supply short-circuit, group error, overflow/underflow

Frequently Asked Questions

What is the exact product type of Siemens 6ES7134-6GB00-0BA1?

It is an AI 2xI 2-/4-wire ST SIMATIC ET 200SP analog input module.

Which BaseUnits and connection variants are supported?

It is suitable for BU type A0 and A1, with 1-wire, 2-wire, and 4-wire connections.

What supply voltage does the module require?

Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.

Which diagnostics are available?

The module supports supply-voltage monitoring, wire-break diagnosis at 4 mA to 20 mA, encoder-supply short-circuit diagnosis, group error, and overflow/underflow.

What information should I provide for a quotation?

Provide the required quantity, destination, requested date, and any project list or configuration details for verification.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote