Product information
Overview
Key Features
- Low-overload power rating: Rated power: 18.50 kW | 25.00 hp (LO); rated current: 37.00 A (LO).
- High-overload power rating: Rated power: 15.00 kW | 20.00 hp (HO); rated current: 31.00 A (HO).
- Input and output ratings: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC, with maximum output current of 62.00 A.
- Control and frequency ranges: Output frequency: 0 … 240 Hz for vector control and 0 … 550 Hz for V/f control. Supported control includes sensorless vector control, V/f control and V/f with flux current control (FCC).
- I/O and communication: The I/O interface has 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input, and 1 non-isolated analog output. Communication: USS/MODBUS RTU.
- Connections and protection: Integrated Class A filter and IP20 / UL open type protection. Line-side, motor-end and DC-link connections use plug-in screw terminals; maximum shielded motor cable length is 50 m (164.04 ft).
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power (LO) | 18.50 kW | 25.00 hp |
| Rated power (HO) | 15.00 kW | 20.00 hp |
| Maximum output current | 62.00 A |
| Output frequency | 0 … 240 Hz vector control; 0 … 550 Hz V/f control |
| I/O | 6 digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input, 1 non-isolated analog output |
| Communication | USS/MODBUS RTU |
| Protection | IP20 / UL open type |
| Frame size | FSC |
Frequently Asked Questions
What is the exact Siemens model and converter type?
It is Siemens 6SL3210-1KE23-8AB1, a SINAMICS G120C compact converter.
What are the low-overload and high-overload ratings?
Low overload: 18.50 kW | 25.00 hp at 37.00 A. High overload: 15.00 kW | 20.00 hp at 31.00 A.
Which control and communication interfaces are available?
It has 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input, 1 non-isolated analog output, and USS/MODBUS RTU communication. Supported control includes sensorless vector control, V/f control and V/f with flux current control (FCC).
What connections and protection does the configuration have?
It has plug-in screw terminals for the line side, motor end and DC link, an integrated Class A filter, and IP20 / UL open type protection.
What details should be included for a quotation request?
Provide the required quantity, destination and requested date for quotation review.