ET 200SP Remote I/O Parts

6ES7193-6TP00-0TP1

Product details

Product Code
6ES7193-6TP00-0TP1
Dimensions
8.4 × 5 × 2.2 cm
Weight
0.029 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • Potential distribution: PotDis-TB-P1-R potential distributor module with 18 x potential P1.
  • Rated voltage: P1 and P2 bus: 48 V maximum; process terminals: 48 V maximum.
  • Current carrying capacity: 10 A maximum up to 60 °C, for the P1 and P2 bus, and for process terminals.
  • Push-In connections: 16 process terminals to the I/O module and 2 terminals with connection to the P1 and P2 bus.
  • Installation conditions: Operating temperature is -30 °C to 60 °C for horizontal installation and -30 °C to 50 °C for vertical installation.

Technical Summary

Product type PotDis-TB-P1-R potential distributor module
Potential P1 18 x
Maximum voltage, P1 and P2 bus 48 V
Maximum voltage, process terminals 48 V
Maximum current carrying capacity 10 A up to 60 °C; 10 A for P1 and P2 bus; 10 A for process terminals
Process terminals 16 to I/O module
P1 and P2 bus terminals 2
Terminal type Push-In terminal
Conductor cross-section 0.14 mm2 min.; 2.5 mm2 max.
Operating temperature -30 °C to 60 °C horizontal; -30 °C to 50 °C vertical
External power-supply protection 10 A miniature circuit breaker with type B or C tripping characteristic for the respective rated supply voltage

Frequently Asked Questions

What is the exact product type of Siemens 6ES7193-6TP00-0TP1?

It is a SIMATIC ET 200SP PotDis-TB-P1-R potential distributor module.

What voltage does the module support?

The maximum rated voltage is 48 V for the P1 and P2 bus and 48 V for the process terminals.

How many terminals are included?

It has 16 process terminals to the I/O module and 2 terminals connected to the P1 and P2 bus.

What installation temperatures are supported?

For horizontal installation, the operating range is -30 °C to 60 °C. For vertical installation, it is -30 °C to 50 °C.

What details should be provided for a quotation?

Provide the required quantity, destination and any project-list or configuration details for verification.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote