Product information
Overview
Applications
- Electrical measurement: Measures voltage, current, energy, frequency, active power, reactive power and power factor.
- Electrical line analysis: Performs line analysis using instantaneous and half-wave monitoring, THD measurement, harmonic measurement, voltage-dip detection and voltage-swell detection.
Key Features
- Energy and power measurement: Measures voltage, current, energy, frequency, active power, reactive power, power factor and active or reactive energy.
- Current transformer input: Supports current measurement with a 1 A or 5 A current transformer; maximum 4 current measurements.
- Line analysis functions: Provides monitoring of instantaneous and half-wave values, THD measurement, harmonics, voltage dip and voltage swell.
- Interfaces and diagnostics: Supports PROFIBUS with GSD Revision 3 and 5 and higher, PROFINET GSD V2.3, diagnostic alarms and channel diagnostics.
- Supply and mounting: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Mounting position is any and the usable BaseUnit is BU type U0.
- Measured-value performance: All channels have a typical cycle time of 50 ms for consistent updates. Maximum sampling frequency is 2 048 kHz and measured-value acquisition bandwidth is 3.2 kHz.
Technical Summary
| Product type | AI Energy Meter CT HF |
|---|---|
| Current transformer | 1 A or 5 A current transformer |
| Maximum current measurement | Max. 4 |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Usable BaseUnit | BU type U0 |
| Communication | PROFIBUS GSD Revision 3 and 5 and higher; PROFINET GSD V2.3 |
| Typical cycle time | 50 ms; all channels |
| Maximum sampling frequency | 2 048 kHz |
| Voltage measurement | 3 V to 300 V phase to neutral; 6 V to 519 V between line conductors |
| Operating temperature | -30 °C to 60 °C horizontal installation; -30 °C to 50 °C vertical installation |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7134-6PA01-0CU0?
It is an AI Energy Meter CT HF analog input module for SIMATIC ET 200SP.
Which current transformers does this module support?
It supports a 1 A or 5 A current transformer and supports a maximum of 4 current measurements.
Which BaseUnit is usable for this module?
The usable BaseUnit is BU type U0.
What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
What information should I provide for a quotation?
Provide the required quantity, destination and project list or verification context for 6ES7134-6PA01-0CU0.