Product information
Overview
Applications
- Safety-oriented load-group shutdown: Supports safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
Key Features
- Digital output capacity: 8 parameterizable, current-sourcing transistor outputs; 8 channels in groups of 8.
- Output ratings: Rated output voltage: 24 V DC. Rated output current: 2 A per channel; maximum current per group: 8 A and per module: 16 A.
- PWM function: Up to 2 outputs can be used for PWM. Cycle duration is parameterizable from 2 … 100 ms continuous, with 0.1 % duty-cycle resolution and a 300 μs minimum pulse duration.
- Diagnostics and substitute values: Diagnostics, diagnostic alarms, maintenance interrupt, group error, short-circuit monitoring and connectable substitute values are supported.
- Supply and protection: Rated supply voltage: 24 V DC, with a permissible range of 19.2 V to 28.8 V. Reverse polarity protection is provided through internal protection with 10 A per group.
- Safety-oriented shutdown: Supports safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
Technical Summary
| Product type | DQ 8x24VDC/2A HF |
|---|---|
| Digital outputs | 8 transistor outputs, current-sourcing |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 2 A per channel |
| Maximum current per group | 8 A |
| Maximum current per module | 16 A |
| PWM outputs | Maximum 2 |
| PWM cycle duration | 2 … 100 ms continuous |
| Firmware version | V2.2.0 |
| PROFINET GSD version | V2.3 |
| Front connector | Screw terminals or push-in; ordered separately |
Frequently Asked Questions
What is the output capacity of Siemens 6ES7522-1BF00-0AB0?
It has 8 transistor outputs, with a rated output current of 2 A per channel, a maximum of 8 A per group and 16 A per module.
How many outputs support PWM?
A maximum of 2 outputs can be used for PWM. PWM support requires FS02 and firmware V2.1.0 or higher.
What supply voltage does this module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Is the front connector included?
The module is supplied without the front connector; screw terminals or push-in connectors must be ordered separately.