Product information
Overview
Applications
- Controlling a digital input: The module supports controlling a digital input.
Key Features
- Relay outputs: 2 digital relay outputs with isolated change-over contacts and potential separation between channels, channels and backplane bus, and channels and load voltage L+.
- Output ratings: Output current for signal "1": 5 A rated value; minimum load current: 8 mA. See data in manual.
- Load voltage: Rated load voltage L+: 24 V DC, from power module, with reverse polarity protection.
- Switching frequency: Maximum switching frequency is 2 Hz with resistive load, 0.5 Hz with inductive load, and 2 Hz on lamp load.
- Installation limits: For horizontal installation, maximum current is 5 A per channel up to 50 °C or 4 A per channel up to 60 °C. For vertical installation, maximum current is 5 A per channel up to 40 °C.
- Configuration and lifecycle: 15 mm width, substitute values connectable as 0/1, and product cancellation. The relay outputs have no short-circuit protection and must be fused externally with 6 A.
Technical Summary
| Product | 6ES7132-4HB13-0AB0 |
|---|---|
| Family | SIMATIC DP ET 200S electronic module |
| Digital outputs | 2 relay outputs |
| Load voltage | 24 V DC, from power module |
| Output current | 5 A rated value for signal "1"; 8 mA minimum load current |
| Output contacts | Isolated change-over contacts |
| Switching frequency | 2 Hz resistive; 0.5 Hz inductive; 2 Hz lamp load, maximum |
| Installation current | 5 A per channel up to 50 °C horizontal; 4 A per channel up to 60 °C horizontal; 5 A per channel up to 40 °C vertical |
| Substitute values | Connectable as 0/1 |
| Packing unit | 5 units per packing unit |
| Protection note | No short-circuit protection; external 6 A fusing required |
Frequently Asked Questions
What outputs does the Siemens 6ES7132-4HB13-0AB0 have?
It has 2 digital relay outputs with isolated change-over contacts.
What load voltage does this module use?
The rated load voltage L+ is 24 V DC from the power module, with reverse polarity protection.
What current can each channel switch?
For horizontal installation, the maximum is 5 A per channel up to 50 °C or 4 A per channel up to 60 °C. For vertical installation, it is 5 A per channel up to 40 °C.
Does the module include short-circuit protection?
It is without short-circuit protection. The relay outputs must be fused externally with 6 A.
What information should I provide for a quotation?