Product information
Overview
Applications
- Incremental encoder counting: Counts signals from one symmetrical incremental encoder, including A/B tracks with 90° phase offset and optional zero track.
- Frequency and cycle-duration measurement: Measures frequency from 0.04 Hz to 800 kHz with quadruple evaluation and cycle duration from 1 μs to 25 s.
- Safe speed and direction monitoring: Supports Safe Operating Stop (SOS), Safely-Limited Speed (SLS), Safe Direction (SDI), and Safe Speed Monitor (SSM).
Key Features
- Encoder channel and signal: 1 channel for symmetrical incremental encoders; sin/cos 1 Vpp input, centered at 2.5 V offset.
- Counting performance: Input frequency up to 200 kHz and counting frequency up to 800 kHz with quadruple evaluation.
- Encoder supply: 5.1 V ±3.5 % encoder supply with output current up to 300 mA and electronic overload protection; no protection on applying a normal or counter voltage.
- PROFIsafe safety functions: Supports Safe Operating Stop (SOS), Safely-Limited Speed (SLS), Safe Direction (SDI), and Safe Speed Monitor (SSM).
- Diagnostics and status: Provides supply-voltage, wire-break, short-circuit, and A/B transition diagnostics, with RUN, ERROR, PWR, channel-status, channel-diagnostics, and module-diagnostics LEDs.
- Mounting and supply: Suitable for BU type A0; rated supply voltage is 24 V DC and load voltage L+ is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
Technical Summary
| Product type | F-TM Count 1x1Vpp sin/cos HF |
|---|---|
| Channel capacity | 1 channel; 1 counter |
| Input signal | sin/cos 1 Vpp, centered at 2.5 V offset |
| Input frequency, max. | 200 kHz |
| Counting frequency, max. | 800 kHz; with quadruple evaluation |
| Encoder supply | 5.1 V ±3.5 %; output current up to 300 mA |
| Rated supply voltage | 24 V DC |
| Load voltage L+, permissible range | 20.4 V to 28.8 V DC |
| Firmware version | V1.0 |
| BaseUnit | BU type A0 |
| Product lifecycle | Active Product |
Frequently Asked Questions
What encoder signal does Siemens 6ES7136-6CB00-0CA0 support?
It supports symmetrical incremental encoders with sin/cos 1 Vpp signals centered at 2.5 V offset, including A/B tracks with 90° phase offset and optional zero track.
What are the maximum input and counting frequencies?
The maximum input frequency is 200 kHz. The maximum counting frequency is 800 kHz with quadruple evaluation.
Which BaseUnit is suitable for this module?
The module is suitable for BU type A0.
Does the module include RS 485 interfaces?
No. The number of RS 485 interfaces is 0.
How can I request a quotation for this exact module?
Send the required quantity, destination, requested date, and any project-list context for quotation review.