Product information
Overview
Applications
- Safety-oriented load-group shutdown: Supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
Key Features
- Analog output capacity: 8 analog output channels, with voltage ranges of 0 to 10 V, 1 V to 5 V and -10 V to +10 V, plus current ranges of 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Resolution and accuracy: 16-bit resolution; operational error limit is (+/-) 0.3% relative to the output range for voltage and current.
- Oversampling performance: Oversampling is supported with 16 values per cycle and a minimum cycle time of 125 μs for all channels, independent of the number of activated channels.
- Diagnostics and substitute values: Diagnostics, diagnostic alarms, supply-voltage monitoring and connectable substitute values are supported. Wire-break detection applies only to current output; short-circuit detection applies only to voltage output.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC and reverse polarity protection. Voltage output short-circuit protection is supported.
- Delivery configuration: Delivery includes the infeed element, shielding bracket and shield terminal. The front connector with screw terminals or push-in must be ordered separately.
Technical Summary
| Product type | AQ 8xU/I HS |
|---|---|
| Analog outputs | 8 |
| Resolution | 16 bit |
| Operational error limit | Voltage: (+/-) 0.3%; current: (+/-) 0.3%, relative to the output range |
| Rated supply | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Minimum cycle time | 125 μs; all channels, independent of the number of activated channels |
| Oversampling values per cycle | 16 |
| Firmware version | V2.1.0 |
| Output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Front connector | Screw terminals or push-in; ordered separately |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7532-5HF00-0AB0?
The product type designation is AQ 8xU/I HS, a SIMATIC S7-1500 analog output module.
How many analog outputs does the module have?
It has 8 analog output channels.
What connector is included with the module?
The delivery includes the infeed element, shielding bracket and shield terminal. The front connector with screw terminals or push-in is ordered separately.
What supply voltage does the module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.