Product information
Overview
Applications
- Counter input operation: Up to 2 digital inputs can be used as counters with a maximum counting frequency of 6 kHz under FS04 and firmware V2.2.1 or higher.
- Gate start/stop control: Parameterizable digital input functions include gate start/stop.
Key Features
- 32 digital inputs: Provides 32 parameterizable digital inputs with 24 V DC rated input voltage.
- Counter capability: Up to 2 inputs can be used as counters with a maximum counting frequency of 6 kHz under FS04 and firmware V2.2.1 or higher; counting width is 32 bit.
- Configurable input delay: Standard input delay is parameterizable from 0.05 ms to 20 ms.
- Diagnostics and interrupts: Provides diagnostics, diagnostic alarms, hardware interrupts, supply-voltage monitoring and wire-break diagnosis to I < 350 μA.
- Flexible connection options: The front connector uses screw terminals or push-in terminals and must be ordered separately.
- SIMATIC engineering support: STEP 7 TIA Portal is configurable/integrated from V13 SP1, and STEP 7 is configurable/integrated from V5.5 SP3.
Technical Summary
| Product type designation | DI 32x24VDC HF |
|---|---|
| Product lifecycle | Active Product |
| Digital inputs | 32 |
| Input voltage, rated value (DC) | 24 V |
| Permissible supply-voltage range | 19.2 V to 28.8 V DC |
| Counter inputs, max. | 2 |
| Counting frequency, max. | 6 kHz; FS04 and FW V2.2.1 or higher |
| Input delay | 0.05 ms to 20 ms |
| Address space per module, inputs | 4 byte |
| Firmware version | V2.2.1 |
Frequently Asked Questions
What is the exact Siemens model and input type?
The exact model is Siemens 6ES7521-1BL00-0AB0, product type designation DI 32x24VDC HF.
How many digital inputs does the module provide?
It has 32 parameterizable digital inputs with a rated input voltage of 24 V DC.
Can the inputs be used as counters?
Yes. Up to 2 inputs can be used as counters with a maximum counting frequency of 6 kHz under FS04 and firmware V2.2.1 or higher.
Is the front connector included?
It is without the front connector; screw-terminal or push-in front connectors must be ordered separately.