Product information
Overview
Applications
- Frequency measurement: The source specifies frequency measurement as a supported counter function, with counting frequency up to 100 kHz.
- Controlled positioning: The source specifies controlled positioning as a supported counter function.
- PID control: The source specifies a PID controller as a supported counter function.
Key Features
- Integrated digital I/O: 8 digital inputs and 6 relay outputs are integrated; relay output switching capacity is 2 A with resistive load, maximum.
- Analog input capacity: 2 analog inputs support 0 to +10 V; resolution with overrange is 10 bit maximum and conversion time is 625 μs per channel.
- PROFINET interface: 1 isolated PROFINET interface with RJ 45 (Ethernet), automatic transmission-rate detection, autonegotiation and autocrossing.
- Supply and memory: Power supply is DC 20.4-28.8V DC; integrated work memory is 50 kbyte and load memory is 1 Mbyte.
- Programming package: Engineering uses STEP 7 V11 SP2 or higher.
- Protection and diagnostics: The CPU has IP20 protection, a diagnostic buffer, forcing, and status/control for inputs/outputs, memory bits, DBs, distributed I/Os, timers and counters.
Technical Summary
| Product type | CPU 1212C DC/DC/relay |
|---|---|
| Integrated digital inputs | 8; 24 V DC |
| Integrated digital outputs | 6; Relays |
| Analog inputs | 2; 0 to +10 V |
| PROFINET interfaces | 1; isolated |
| Power supply | DC 20.4-28.8V DC |
| Work memory | 50 kbyte |
| Load memory | 1 Mbyte |
| Programming package | STEP 7 V11 SP2 or higher |
| Processing time, bit operations | 0.085 μs / instruction; typical |
| Protection | IP20 |
Frequently Asked Questions
What is the exact configuration of Siemens 6ES7212-1HE31-0XB0?
It is a SIMATIC S7-1200 CPU 1212C with DC/DC/relay configuration and onboard I/O.
How many digital and analog channels does it have?
It has 8 digital inputs, 6 relay outputs and 2 analog inputs. The analog inputs support 0 to +10 V.
What supply voltage does the CPU use?
The permissible DC supply range is 20.4 V to 28.8 V.
Which communication interface and protocols are supported?
It has 1 PROFINET interface and supports PROFINET IO Controller, PROFIBUS, TCP/IP, ISO-on-TCP (RFC1006), UDP and MODBUS.
What information should be included in a quotation request?
Provide the required quantity, destination and project-list context for model-specific quotation support.