Product information
Overview
Key Features
- Two analog voltage outputs: The module has 2 analog outputs with two-wire actuator connection and a minimum load impedance of 2 kΩ for voltage outputs.
- Selectable voltage ranges: Supported ranges are 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V.
- Resolution and cycle time: Maximum resolution is 16 bit including sign, with a minimum cycle time of 1 ms for all channels.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics and system integration: The module provides module diagnostics, diagnostic alarms, supply-voltage monitoring, short-circuit and overflow/underflow diagnoses, and supports PROFINET GSDML V2.3 and PROFIBUS GSD Revision 5.
Technical Summary
| Product type | AQ 2xU ST |
|---|---|
| Analog outputs | 2 |
| Voltage output ranges | 0 to 10 V; 1 V to 5 V; -5 V to +5 V; -10 V to +10 V |
| Maximum resolution | 16 bit including sign |
| Cycle time, min. | 1 ms (all channels) |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Load impedance, min. | 2 kΩ (voltage outputs) |
| Usable BaseUnits | BU type A0, A1 |
| Firmware version | V1.0.3 |
| Module diagnostics | Yes |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7135-6FB00-0BA1?
The product type designation is AQ 2xU ST.
Which voltage ranges does the module support?
It supports 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V.
What supply voltage does the module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which BaseUnits can be used with this configuration?
Usable BaseUnits are BU type A0 and BU type A1.