Product information
Overview
Key Features
- Power and overload ratings: Rated power: 0.55 kW | 0.75 hp (LO) and 0.37 kW | 0.50 hp (HO). Low overload: 150% for 3 s, 110% for 57 s, and 100% for 240 s at 0.55 kW; high overload: 200% for 3 s, 150% for 57 s, and 100% for 240 s at 0.37 kW.
- Input and output: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC; maximum output current: 2.60 A.
- Frequency performance: Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency: 4 kHz.
- Integrated functions: Integrated Class A filter and braking chopper. Released as of CU firmware version V4.6.
- Connections and mounting: Line-side and motor-end connections use plug-in screw terminals for 1.00 … 2.50 mm2 (AWG 18 … AWG 14) conductors. Frame size: FSA; dimensions: 196 mm H x 73 mm W x 165 mm D.
Technical Summary
| Product type | SINAMICS Power Module PM240-2 |
|---|---|
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated power (LO) | 0.55 kW | 0.75 hp |
| Rated power (HO) | 0.37 kW | 0.50 hp |
| Rated current (LO) | 1.70 A output; 2.30 A input |
| Rated current (HO) | 1.30 A output; 2.00 A input |
| Maximum output current | 2.60 A |
| Output frequency | 0 … 200 Hz vector control; 0 … 550 Hz V/f control |
| Integrated filter | Class A |
| Protection | IP20 / UL open type |
| Frame size | FSA |
| Firmware release | CU firmware version V4.6 |
Frequently Asked Questions
What is the exact product type?
It is the Siemens SINAMICS Power Module PM240-2, order number 6SL3210-1PE11-8AL1.
What supply does this power module use?
Input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.
What connections and conductor sizes are supported?
The line side and motor end use plug-in screw terminals for 1.00 … 2.50 mm2 (AWG 18 … AWG 14) conductors.
Does the configuration include a Control Unit and operating unit?
It is without a Control Unit and operating unit.
What information should I include for a quotation?
Send the required quantity, destination, requested date, and project or item-list context for quotation review.