Product information
Overview
Applications
- Electrical measurement: Measures voltage, current, energy, frequency, active power, and reactive power.
Key Features
- Measurement functions: Measures voltage, current, energy, frequency, active power, reactive power, and power.
- Voltage measurement: Measures 230 V between phase and neutral conductor and 400 V between line conductors; measurable ranges are 90 V to 264 V and 155 V to 460 V respectively.
- Current measurement: Measures 5 % to 100 % of the secondary rated current for 1 A or 5 A current transformers.
- Measurement performance: TRMS voltage and current measurement with 50 ms typical cycle time for consistent updates of all measured and calculated values; bandwidth is 2 kHz.
- Interfaces and diagnostics: Has 32 byte input and 12 byte output address space, diagnostic alarm, PWR-LED, green channel-status LED, red Fn LED, and green/red DIAG LED.
Technical Summary
| Product type | AI energy meter 400VAC ST |
|---|---|
| Firmware version | V3.0 |
| Usable BaseUnit | BU type D0 |
| Supply voltage | 100 – 240 V AC |
| Permissible supply range | 90 V to 264 V AC; 47 Hz to 63 Hz |
| Voltage measurement | 230 V phase-to-neutral; 400 V between line conductors |
| Current measurement | 5 % to 100 % of secondary rated current; 1 A, 5 A |
| Measurement procedure | TRMS; seamless measured value acquisition |
| Cycle time | 50 ms, typ. (all channels) |
| Bandwidth | 2 kHz |
| Mounting position | any |
Frequently Asked Questions
What product is Siemens 6ES7134-6PA01-0BD0?
It is a SIMATIC ET 200SP analog input module, AI energy meter 400VAC ST, for BU type D0.
What voltage can this module measure?
It measures 230 V between phase and neutral conductor and 400 V between line conductors. The measurable ranges are 90 V to 264 V and 155 V to 460 V respectively.
What current transformer range is supported?
The measurable relative current is 5 % to 100 % of the secondary rated current for 1 A or 5 A current transformers.
Does it provide channel diagnostics?
Yes. It has a diagnostic alarm, channel status display with green LED, red Fn LED for channel diagnostics, and green/red DIAG LED for module diagnostics.
What information should I include for a quotation?
Include the required quantity, destination, requested date, and any project-list context for verification.