Product information
Overview
Applications
- Digital signal switching: The digital outputs switch resistive and inductive loads, with switching functions parameterizable by comparison values.
- Counter signal processing: The digital inputs process counter signals with up/down counting and a maximum counting frequency of 2 kHz.
- Module diagnostics: The module provides short-circuit diagnoses, diagnostic alarms, load-voltage monitoring, and channel-status indication.
Key Features
- Digital I/O capacity: 16 digital inputs and 16 digital outputs are parameterizable as DIQ.
- 24 V DC supply: Load voltage 1L+ and 2L+ have a rated value of 24 V DC, with a permissible range of 20.4 V to 28.8 V.
- Counter function: Up to 4 counters are parameterizable, with a maximum counting frequency of 2 kHz and 32 bit counting width including sign.
- Digital output performance: Outputs provide a rated signal-1 current of 0.5 A, with short-circuit protection per channel and a maximum resistive-load switching frequency of 100 Hz.
- Connections and protection: The module has 8xM12 connections and IP65/67 protection.
- Diagnostics and configuration: It supports parameterizable diagnostic alarms, channel-by-channel substitute values, green channel-status LEDs, and STEP 7 TIA Portal from V14 or higher.
Technical Summary
| Order number | 6ES7143-5AH00-0BA0 |
|---|---|
| Product type designation | DIQ 16x24VDC/0.5A |
| Digital inputs | 16; parameterizable as DIQ |
| Digital outputs | 16; parameterizable as DIQ |
| Load voltage | 1L+ and 2L+, rated value 24 V DC; permissible range 20.4 V to 28.8 V |
| Counter capacity | 4 counters maximum; 2 kHz maximum counting frequency; 32 bit counting width including sign |
| Output current | 0.5 A rated value for signal "1" |
| Connections | 8xM12 |
| Protection | IP65/67 |
| Firmware version | V2.0.x |
| HW functional status | FS06 |
Frequently Asked Questions
What I/O capacity does Siemens 6ES7143-5AH00-0BA0 provide?
It has 16 digital inputs and 16 digital outputs, both parameterizable as DIQ.
What supply voltage does the module use?
Load voltages 1L+ and 2L+ have a rated value of 24 V DC, with a permissible range of 20.4 V to 28.8 V.
How many counter functions are available?
Up to 4 counters are parameterizable. The maximum counting frequency is 2 kHz, with 32 bit counting width including sign.
What connections and protection are provided?
The module has 8xM12 connections and IP65/67 protection.
Can you quote this exact Siemens module for a project?
Send the required quantity, destination, requested date, and project list for model-specific quotation support.