Overview
Applications
- Digital signal control: Controls digital inputs; parallel switching of two outputs is supported for redundant control of a load.
Key Features
- Digital output capacity: 8 parameterizable digital outputs with source output (PNP, current-sourcing).
- Output current: Rated output current is 0.5 A per channel; maximum total current is 4 A per module.
- Supply voltage: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics: Channel-by-channel short-circuit and wire-break diagnostics, supply-voltage monitoring, diagnostic alarm, and green/red diagnostic LEDs.
- Output switching: Maximum switching frequency is 100 Hz with resistive load, 2 Hz with inductive load, and 10 Hz on lamp load.
- BaseUnit and connection: Uses BU type A0 for 1-wire and 2-wire connections; 3-wire connection uses BU type A0 with AUX terminals or a potential distributor module, while 4-wire connection uses BU type A0 + Potential distributor module.
Technical Summary
| Product type designation | DQ 8×24 V DC/0.5 A HF |
|---|---|
| Digital outputs | 8 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 0.5 A per channel |
| Maximum total current | 4 A per module |
| Short-circuit protection | Yes |
| Wire-break diagnosis | Yes; channel by channel |
| BaseUnit | BU type A0 |
| PROFINET GSDML | V2.3 |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact Siemens model and output configuration?
It is Siemens 6ES7132-6BF00-0CA0, a SIMATIC ET 200SP digital output module with 8 DQ channels, 24 V DC, and 0.5 A output current.
What supply voltage does the module use?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC.
What diagnostics are supported?
The module supports channel-by-channel short-circuit and wire-break diagnostics, supply-voltage monitoring, diagnostic alarms, and channel and module diagnostic LEDs.
Which BaseUnit is used for connection?
BU type A0 is used for 1-wire and 2-wire connections. A 3-wire connection uses BU type A0 with AUX terminals or a potential distributor module; a 4-wire connection uses BU type A0 + Potential distributor module.
What should I include in a quotation request?
Include the required quantity, destination, requested date, and any project-list context for verification.