S7-400 PLC Parts

6ES7422-1HH00-0AA0

Product details

Product Code
6ES7422-1HH00-0AA0
Dimensions
29.9 × 23.1 × 3.8 cm
Weight
0.879 kg
Lifecycle
Announcement of product phase-out
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Applications

  • Controlling digital inputs: The digital outputs can control a digital input.

Key Features

  • Digital output capacity: 16 isolated digital outputs using relays.
  • Rated load voltage: Load voltage is 60 V DC or 230 V AC.
  • Output current: Rated output current for signal "1" is 5 A; minimum load current is 11 mA.
  • Switching frequency: Maximum switching frequency is 10 Hz with a resistive load, 1 Hz with an inductive load or lamp load, and 20 Hz mechanically.
  • Channel separation: Digital outputs have potential separation between channels, in groups of 2, and between the channels and backplane bus.
  • Lifecycle status: Announcement of product phase-out.

Technical Summary

Product SIMATIC S7-400, digital output SM 422
Digital outputs 16; Relays
Output current, signal "1", rated value 5 A
Load voltage, rated value (DC) 60 V
Load voltage, rated value (AC) 230 V
Permissible load voltage range (DC) 1 V to 60 V
Permissible load voltage range (AC) 2 V to 264 V
Short-circuit protection No
Input current from backplane bus, 5 V DC, max. 1 A
Power loss, typical 4.5 W
Lifecycle Announcement of product phase-out

Frequently Asked Questions

What is the exact Siemens model and output configuration?

It is Siemens 6ES7422-1HH00-0AA0, a SIMATIC S7-400 SM 422 digital output module with 16 isolated relay outputs.

What load voltage and output current does it support?

The rated load voltage is 60 V DC or 230 V AC. Rated output current for signal "1" is 5 A, with a minimum load current of 11 mA.

Does the module have short-circuit protection?

It has no short-circuit protection.

How are the digital outputs electrically separated?

Potential separation exists between the channels, in groups of 2, and between the channels and the backplane bus.

What details should be included for a quotation request?

Include the required quantity, destination, and project or MRO list context for model-specific quotation support.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote