Product information
Overview
Key Features
- 8 analog input channels: Supports 8 channels for current and voltage measurement, with 4 channels for resistance thermometer measurement and 8 channels for thermocouple measurement.
- 16-bit resolution and accuracy: Resolution with overrange is 16 bit; operational error limit for voltage, current and resistance is 0.3% relative to the input range.
- Flexible signal ranges: Supported rated input ranges include 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Diagnostics and interrupts: Has diagnostics, diagnostic and limit value alarms, wire-break monitoring for 1 V to 5 V, 4 mA to 20 mA, TC, R and RTD, plus hardware interrupts.
- 24 V supply: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Included components: Delivery includes an infeed element, shield bracket and shield terminal. The front connector with screw terminals or push-in must be ordered separately.
Technical Summary
| Product type | AI 8xU/I/RTD/TC ST |
|---|---|
| Analog inputs | 8 |
| Resolution | 16 bit |
| Accuracy | 0.3% |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Input resistance | 100 kΩ for 1 V to 5 V; 10 MΩ for -1 V to +1 V |
| Supported thermocouple types | B, E, J, K, N, R, S and T |
| Firmware version | V2.0.0 |
| PROFINET GSD | V2.3 |
| PROFIBUS GSD | V1.0 / V5.1 |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7531-7KF00-0AB0?
It is a SIMATIC S7-1500 analog input module, AI 8xU/I/RTD/TC ST.
How many analog input channels does the module have?
It has 8 analog input channels; 4 channels are available for resistance thermometer measurement.
What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Is the front connector included?
The delivery includes an infeed element, shield bracket and shield terminal. The front connector with screw terminals or push-in must be ordered separately.
What information should I include for a quotation?
Include the required quantity, destination and project-list context so the exact model can be verified.