Overview
Key Features
- 32 isolated digital outputs: The SM 322 module has 32 digital outputs with potential separation between channels in groups of 8 and between the outputs and the backplane bus by optocoupler.
- AC load voltage: Rated load voltage is 120 V; the permissible AC range is 79 V to 264 V at 47 Hz to 63 Hz.
- Output current: Signal "1" output current is rated at 1 A. The permissible range is 10 mA to 1 A for 0 to 40 °C and 40 to 60 °C.
- Diagnostics and indicators: Diagnostics detect a blown fuse or missing load voltage. The module has a red group error SF LED and a green digital output status indicator per channel.
- Switching capacity and frequency: Maximum switching capacity on lamp load is 50 W. Maximum switching frequency is 10 Hz with resistive load, 0.5 Hz with inductive load, and 1 Hz on lamp load.
- Mechanical configuration: The module has a double-width design, requires a 20-pin front connector, and measures 80 mm wide, 125 mm high, and 117 mm deep.
Technical Summary
| Product type | SIMATIC S7-300 SM 322 isolated digital output module |
|---|---|
| Digital outputs | 32 |
| Rated load voltage | 120 V; 120/230 V AC |
| Permissible load voltage range | 79 V to 264 V AC |
| Permissible frequency range | 47 Hz to 63 Hz |
| Rated output current | 1 A for signal "1" |
| Output current range | 10 mA to 1 A for 0 to 40 °C and 40 to 60 °C |
| Short-circuit protection | No |
| Front connector | 20-pin |
| Isolation | Between channels in groups of 8; between digital outputs and backplane bus by optocoupler |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact Siemens model and module type?
It is Siemens 6ES7322-1FL00-0AA0, a SIMATIC S7-300 SM 322 isolated digital output module.
How many digital outputs does the module have?
It has 32 digital outputs.
What load voltage and output current does it support?
Rated load voltage is 120 V; 120/230 V AC. Signal "1" output current is rated at 1 A, with a permissible range of 10 mA to 1 A for 0 to 40 °C and 40 to 60 °C.
Which connector and dimensions should be verified?
The required front connector is 20-pin. Dimensions are 80 mm wide, 125 mm high, and 117 mm deep.
What should be included in an inquiry for this configuration?
Please provide the required quantity, destination, and project or MRO context for quotation review.