Product information
Overview
Key Features
- Digital output capacity: Has 8 isolated digital outputs with electronic short-circuit protection and a green status indicator per channel.
- Load voltage: Rated load voltage L+ is 24 V DC, with a permissible range from 20.4 V to 28.8 V.
- Output current: Rated output current for signal "1" is 2 A; the permissible range is 5 mA to 2.4 A for 0 to 40 °C and 5 mA to 2.4 A for 40 to 60 °C.
- Output timing: Maximum output delay with resistive load is 100 μs from "0" to "1" and 500 μs from "1" to "0".
- Isolation and connection: Digital outputs have potential separation between channels in groups of 4 and from the backplane bus by optocoupler. The required front connector is 20-pin.
- Installation and dimensions: Total output current per group is 4 A for horizontal installation up to 40 °C or 60 °C and for vertical installation up to 40 °C. Dimensions are 40 mm × 125 mm × 120 mm.
Technical Summary
| Product type | SIMATIC S7-300 digital output SM 322 module |
|---|---|
| Digital outputs | 8 |
| Rated load voltage | 24 V DC |
| Permissible load voltage | 20.4 V to 28.8 V DC |
| Rated output current | 2 A for signal "1" |
| Output current range | 5 mA to 2.4 A |
| Front connector | 20-pin |
| Output isolation | Between channels in groups of 4; from backplane bus by optocoupler |
| Total output current per group | 4 A under stated installation and temperature conditions |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact product type?
It is the Siemens 6ES7322-1BF01-0AA0 SIMATIC S7-300 digital output SM 322 module.
How many digital outputs does it have?
It has 8 isolated digital outputs with a green status indicator per channel.
What load voltage and output current does it use?
The rated load voltage is 24 V DC, and the rated output current for signal "1" is 2 A.
What front connector is required?
A 20-pin front connector is required.
What should be included in a quotation request?
Please provide the required quantity, destination, and project-list context for quotation review.