Product information
Overview
Applications
- Controlling a digital input: The digital output can control a digital input according to IEC 61131-2, type 2.
Key Features
- Fail-safe digital outputs: 8 digital outputs support current-sinking and current-sourcing operation, with short-circuit protection and open-circuit detection.
- Output capacity: Rated output current is 2 A per channel; maximum switching capacity is 2 A with resistive load and 10 W with lamp load.
- Supply voltage: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC and reverse polarity protection.
- Diagnostics: Diagnostics include supply-voltage monitoring, wire-break, short-circuit, group error, and diagnostic alarms.
- PROFIsafe and engineering: The module uses PROFIsafe and is configurable or integrated with STEP 7 TIA Portal from V13 SP1 with HSP 0086.
- Installation and isolation: The module is 35 mm wide; channels are isolated from the backplane bus, while the channels are not isolated from one another.
Technical Summary
| Product type | F-DQ 8x24VDC/2A PPM |
|---|---|
| Digital outputs | 8 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 2 A per channel |
| Maximum resistive-load capacity | 2 A |
| Maximum lamp-load capacity | 10 W |
| Engineering | STEP 7 TIA Portal configurable/integrated from V13 SP1 with HSP 0086 |
| Firmware update | Possible |
| Product function | I&M0 to I&M3 |
| Product lifecycle | Active Product |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7526-2BF00-0AB0?
The product type designation is F-DQ 8x24VDC/2A PPM.
How many digital outputs does the module have?
It has 8 digital outputs with current-sinking and current-sourcing operation.
What supply voltage does the module use?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC.
What diagnostics are supported?
It supports supply-voltage monitoring, wire-break, short-circuit, group error, and diagnostic alarms.
What information should be included in a quotation request?
Include the required quantity, destination, and project-list context for MRO or project quotation review.