Product information
Overview
Applications
- Safety-oriented load-group shutdown: Supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
Key Features
- Digital output capacity: 16 parameterizable transistor output channels, arranged in groups of 1; current-sinking and current-sourcing are supported.
- Output ratings: Rated output values are 24 V, 48 V and 125 V DC, plus 24 V and 48 V AC at 50 – 60 Hz.
- Current capacity: The rated output current is 0.5 A per channel; maximum current is 0.5 A per group and 8 A per module.
- Switching performance: Maximum switching frequency is 25 Hz with resistive load, 0.5 Hz with inductive load and 10 Hz with lamp load.
- System functions: MSO, prioritized startup, I&M0 to I&M3 and substitute values are supported; PWM, oversampling and short-circuit protection are not supported.
- Connection and isolation: The front connector with screw terminals or push-in must be ordered separately. Channels are electrically separated, with isolation tested at 2 000 V DC.
Technical Summary
| Product | 6ES7522-5EH00-0AB0 |
|---|---|
| Product type | DQ 16×24 … 48 V UC/125 V DC/0.5 A ST |
| Digital outputs | 16 transistor channels, in groups of 1 |
| Rated output voltage | 24 V; 48 V; 125 V DC; 24 V; 48 V AC (50 – 60 Hz) |
| Rated output current | 0.5 A per channel |
| Maximum current per module | 8 A |
| Output address space | 2 byte |
| Power consumption | 2 W from the backplane bus |
| Firmware version | from V1.0.0 |
| Front connector | Screw terminals or push-in, ordered separately |
| Protection | No short-circuit protection |
| Safety function | Load-group shutdown up to SIL2; Category 3 / PL d |
Frequently Asked Questions
What output capacity does the Siemens 6ES7522-5EH00-0AB0 provide?
It has 16 transistor output channels in groups of 1, with 0.5 A rated current per channel and 0.5 A maximum current per group.
Which output voltages are supported?
Rated output values are 24 V, 48 V and 125 V DC, plus 24 V and 48 V AC at 50 – 60 Hz.
Is short-circuit protection included?
No. The module has no short-circuit protection.
What connector is included with the module?
The front connector with screw terminals or push-in is not included and must be ordered separately.