Product information
Overview
Key Features
- BaseUnit configuration: BU15-P16+A10+2D with BU type A0, Push-in terminals, 10 AUX terminals, and a new load group.
- Current carrying capacity: Maximum current is 10 A for the P1 and P2 bus and 10 A for the AUX bus; process terminals have a maximum of 2 A.
- Terminal capacity: Has 16 process terminals to the I/O module, 10 terminals to the AUX bus, and 2 terminals with connection to the P1 and P2 bus.
- Supply and protection: Rated supply voltage is 24 V DC. External protection is a 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic.
- Installation dimensions: Dimensions are 15 mm wide, 141 mm high, and 35 mm deep; weight is approximately 50 g.
- Operating temperature: For horizontal installation, ambient temperature during operation is -30 °C to 60 °C; for vertical installation, it is -30 °C to 50 °C.
Technical Summary
| Product type | BU type A0 |
|---|---|
| Configuration | BU15-P16+A10+2D; Push-in terminals; 10 AUX terminals; new load group |
| Rated supply voltage | 24 V DC |
| Current carrying capacity, P1 and P2 bus, max. | 10 A |
| Current carrying capacity, AUX bus, max. | 10 A |
| Current carrying capacity, process terminals, max. | 2 A |
| Process terminals to I/O module | 16 |
| Terminals to AUX bus | 10 |
| Horizontal installation, ambient temperature during operation | -30 °C to 60 °C |
| Vertical installation, ambient temperature during operation | -30 °C to 50 °C |
| Protection requirement | 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic |
Frequently Asked Questions
What is the exact configuration of Siemens 6ES7193-6BP20-0DA0?
It is a SIMATIC ET 200SP BaseUnit BU15-P16+A10+2D with BU type A0, Push-in terminals, 10 AUX terminals, and a new load group.
What supply voltage and external protection does this BaseUnit require?
The rated supply voltage is 24 V DC. External protection is a 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic.
What are the terminal and current limits?
The P1 and P2 bus and AUX bus each have a maximum current of 10 A. Process terminals have a maximum of 2 A; there are 16 process terminals and 10 AUX terminals.
What installation temperatures are supported?
For horizontal installation, ambient temperature during operation is -30 °C to 60 °C. For vertical installation, it is -30 °C to 50 °C.
What information should I provide for a quotation?
Provide the required quantity, destination, and any project-list context for Siemens 6ES7193-6BP20-0DA0.