Product information
Overview
Applications
- ET 200M module connection: Connects ET 200M with up to 12 S7-300 modules through PROFINET IO.
- Module maintenance support: Supports module exchange without PG and maintenance support of new IO modules.
Key Features
- Module capacity: Supports up to 12 S7-300 modules per DP device interface.
- PROFINET IO communication: Bus protocol/transmission protocol: PROFINET IO; TCP/IP: No; PROFINET system redundancy (S2): No; MRP: Yes.
- Supply and output: Rated supply: 24 V DC, permissible range 20.4 V to 28.8 V DC. Backplane bus output: 5 V DC, max. 1.5 A.
- Addressing volume: Inputs: 192 byte; outputs: 192 byte.
- Diagnostics and extended functions: Module diagnostics, LINK LED, RX/TX LED, isochronous real time communication class 1 and 2, module exchange without PG, operation without MMC, and maintenance support of new IO modules.
- Protection and installation limits: IP20 protection; operation from 0 °C to 60 °C and at an installation altitude up to 2 000 m above sea level.
Technical Summary
| Product type designation | IM 153-4 PN ST |
|---|---|
| Module capacity | 12 S7-300 modules per DP device interface, max. |
| Bus protocol | PROFINET IO |
| Rated supply | 24 V DC |
| Permissible supply range | 20.4 V to 28.8 V DC |
| Backplane bus output | 5 V DC, max. 1.5 A |
| Addressing volume | Inputs: 192 byte; outputs: 192 byte |
| MRP | Yes |
| Protection | IP20 |
| Operating ambient temperature | 0 °C to 60 °C |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7153-4AA01-0XB0?
The product type designation is IM 153-4 PN ST, a SIMATIC DP connection module for ET 200M.
How many S7-300 modules can this configuration support?
It supports up to 12 S7-300 modules per DP device interface.
What supply voltage does the module use?
The rated supply is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.
Which communication and redundancy functions are provided?
The bus protocol is PROFINET IO. MRP is supported; TCP/IP and PROFINET system redundancy (S2) are not.
What information should I provide for a quotation?
Provide the required quantity, destination, requested date, and any project-list context for verification.