Product information
Overview
Key Features
- Analog output capacity: Has 2 analog current outputs with 16-bit resolution including sign and output ranges of -20 mA to +20 mA and 4 mA to 20 mA.
- ET 200S module format: Electronics module for ET 200S with a width of 15 mm, height of 81 mm and depth of 52 mm.
- Load voltage and protection: Rated load voltage L+ is 24 V DC and reverse polarity protection is provided.
- Output timing: Maximum cycle time for all channels is 250 μs; isochronous mode is supported.
- Actuator connection: Supports two-wire connection for current output; four-wire connection for current output is not supported.
- Diagnostics and isolation: Provides wire-break and group-error diagnostics, a red group-error SF LED, and potential separation between the channels and backplane bus.
Technical Summary
| Product type | SIMATIC DP electronics module for ET 200S |
|---|---|
| Analog outputs | 2 |
| Output ranges | -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | 16 bit including sign |
| Rated load voltage L+ | 24 V DC |
| Cycle time, all channels, max. | 250 μs |
| Current output, no-load voltage, max. | 18 V |
| Load impedance with current outputs, max. | 500 Ω |
| Connection | Two-wire connection for current output; four-wire connection not supported |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is Siemens 6ES7135-4GB52-0AB0?
It is a SIMATIC DP electronics module for ET 200S with 2 analog current outputs.
Which output ranges and resolution does this module provide?
It supports -20 mA to +20 mA and 4 mA to 20 mA output ranges with 16-bit resolution including sign.
What actuator connection is supported?
It supports two-wire connection for current output. Four-wire connection for current output is not supported.
What are the module dimensions and maximum cable length?
The dimensions are 15 mm wide, 81 mm high and 52 mm deep. The maximum shielded cable length is 200 m, or maximum 20 m for TWA 100 μs.
What information should I provide for a quotation?
Provide the required quantity, destination and project-list context for quotation review.