Product information
Overview
Key Features
- PROFIBUS DP interface: Interfaces/bus type: PROFIBUS DP. PROFIBUS is supported, while PROFINET IO and EtherNet/IP are not supported.
- Supply and load voltage: Rated supply voltage: 24 V DC. Rated load voltage 2L+: 24 V DC. Reverse polarity protection is provided against destruction.
- Addressing volume: Inputs: 244 byte. Outputs: 244 byte.
- Communication performance: RS 485 transmission rate: up to 12 Mbit/s, with automatic detection of the transmission rate. SYNC, FREEZE, and direct data exchange are supported.
- Diagnostics and installation features: Diagnostic and hardware interrupts are parameterizable. Hot swapping of modules is possible, and LEDs indicate load voltage, bus fault BF, group error SF, and 24 V supply status.
- Configuration and exclusions: The module includes a termination module. The connection module 6ES7194-4A.00-0AA0 must be ordered separately. Product phase-out is planned.
Technical Summary
| Product type | IM 154-2 DP HF |
|---|---|
| Interface | PROFIBUS DP |
| Rated supply voltage | 24 V DC |
| Rated load voltage 2L+ | 24 V DC |
| Input addressing volume | 244 byte |
| Output addressing volume | 244 byte |
| RS 485 transmission rate, max. | 12 Mbit/s |
| Supported protocols | PROFIBUS; PROFIsafe |
| Diagnostics | Parameterizable diagnostic and hardware interrupts |
| Module swapping | Hot swapping of modules possible |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7154-2AA01-0AB0?
The product type designation is IM 154-2 DP HF, a PROFIBUS DP interface module.
What supply voltage does this interface module require?
The rated supply voltage is 24 V DC, and the rated load voltage 2L+ is 24 V DC.
Which communication protocols and interfaces are supported?
The interface is PROFIBUS DP with PROFIBUS and PROFIsafe support. PROFINET IO and EtherNet/IP are not supported.
Is the connection module included?
The module includes a termination module. The connection module 6ES7194-4A.00-0AA0 must be ordered separately.
What details should be provided for an MRO or project quotation?
Provide the required quantity, destination, requested date, and any project list or verification details.