Product information
Overview
Applications
- Controlling digital inputs: The digital outputs can control a digital input.
- Redundant load control: Two outputs can be used for redundant control of a load.
Key Features
- Digital output capacity: Has 4 digital outputs with Triac switching and zero point detection; current-sourcing is supported, while current-sinking is not.
- Output ratings: Output voltage is 24 V AC to 230 V AC; output current is 2 A per channel and 8 A per module.
- Load capacity: Switching capacity is up to 2 A with resistive load and up to 100 W with lamp load.
- Switching frequency: Maximum switching frequency is 10 Hz with resistive load, 0.5 Hz with inductive load, and 1 Hz with lamp load.
- BaseUnit and coding: Is suitable for BU type B1 and uses mechanical coding element type C; module color code is CC41.
- Protection and indication: Has no short-circuit protection; with BU type B1, a miniature quick-response fuse with 10 A tripping current must be provided. Green PWR and channel-status LEDs and a green/red DIAG LED are provided.
Technical Summary
| Order number | 6ES7132-6FD00-0BB1 |
|---|---|
| Product type designation | DQ 4×24 … 230 V AC/2 A ST |
| Digital outputs | 4 |
| Output type | Triac with zero point detection |
| Output voltage | 24 V AC to 230 V AC |
| Current per channel, max. | 2 A |
| Current per module, max. | 8 A |
| Usable BaseUnits | BU type B1 |
| Firmware version | V1.0 |
| PROFINET GSDML | V2.3 |
| Module diagnostics | No; module diagnostics LED is provided, but channel diagnostics is not |
Frequently Asked Questions
What is the output capacity of Siemens 6ES7132-6FD00-0BB1?
It has 4 digital outputs, with up to 2 A per channel and 8 A per module.
Which BaseUnit is suitable for this module?
It is suitable for BU type B1.
Does the module have short-circuit protection?
It has no short-circuit protection. When using BU type B1, a miniature quick-response fuse with 10 A tripping current must be provided.
What output loads and switching frequencies are supported?
Maximum switching frequency is 10 Hz with resistive load, 0.5 Hz with inductive load, and 1 Hz with lamp load. Switching capacity is up to 2 A with resistive load and 100 W with lamp load.
What information should be included in a quotation request?
Include the required quantity, destination, and project-list context for verification and quotation.