Key Features
- Analog output capacity: Has 4 analog outputs with voltage ranges of 0 to 10 V, 1 V to 5 V and -10 V to +10 V, plus current ranges of 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Supply and protection: Load voltage L+ rated value (DC): 24 V. Reverse polarity protection is provided, and voltage outputs have short-circuit protection.
- Isolation: The analog outputs are isolated from the backplane bus, load voltage L+ and the power supply of the electronics, but not between the channels. Isolation is tested with 500 V DC.
- Diagnostics: Diagnostics function, parameterizable substitute values, parameterizable diagnostic alarms, readable diagnostic information and a red group error SF LED are provided.
- Connection and installation: Requires a 20-pin front connector. Voltage output uses four-wire actuator connection and current output uses two-wire actuator connection; removal and insertion with the active backplane bus is possible.
- Dimensions and weight: Dimensions are 40 mm wide, 125 mm high and 117 mm deep. Weight is approximately 220 g.
Technical Summary
| Product type | SIMATIC S7-300 SM 332 analog output module |
|---|---|
| Analog outputs | 4 |
| Rated load voltage L+ | 24 V DC |
| Voltage output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V |
| Current output ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Voltage output load impedance | 1 kΩ min.; capacitive load 1 μF max. |
| Current output load impedance | 500 Ω max.; inductive load 10 mH max. |
| Conversion time per channel | 0.8 ms |
| Front connector | 20-pin |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact product type and output capacity?
6ES7332-5HD01-0AB0 is a SIMATIC S7-300 SM 332 analog output module with 4 analog outputs.
Which signal ranges does this module support?
Voltage ranges are 0 to 10 V, 1 V to 5 V and -10 V to +10 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
What connector and actuator wiring are required?
The required front connector is 20-pin. Voltage output uses a four-wire actuator connection, while current output uses a two-wire actuator connection.
Does the module provide diagnostics and channel isolation?
It provides parameterizable diagnostics, substitute values and diagnostic alarms, readable diagnostic information and a red group error SF LED. The channels are not isolated from one another, while the outputs are isolated from the backplane bus and load voltage L+.
Can you quote this exact item for a project requirement?
Send the required quantity, destination and project-list context for a model-specific quotation.