Product information
Overview
Key Features
- Digital input capacity: 16 parameterizable digital inputs with a 24 V DC rated input voltage and IEC 61131 type 3 input characteristic.
- PROFINET communication: 1 PROFINET interface with 100 Mbit/s full duplex, 2 M12, 4-pin, D-coded ports, and an integrated switch.
- Supported protocols: Supports PROFINET IO, EtherNet/IP, and Modbus TCP; PROFIsafe is not supported.
- Input diagnostics: Channel diagnostics include wire break at the input and encoder power supply short-circuit detection.
- Supply and encoder outputs: Load voltage 1L+ is 24 V DC, with a permissible range of 20.4 V to 28.8 V. It has 8 encoder supply outputs with short-circuit protection group-by-group for 2 channels.
- Protection and synchronization: IP65/67/69K protection, 0.25 ms isochronous mode, prioritized startup, MSI, and MRP are supported.
Technical Summary
| Product | SIMATIC ET 200eco PN, DI 16x 24 V DC, M12-L, 8x M12 |
|---|---|
| Digital inputs | 16; parameterizable |
| Load voltage 1L+ | 24 V DC; permissible range 20.4 V to 28.8 V |
| PROFINET interfaces | 1; 100 Mbit/s full duplex (100BASE-TX) |
| M12 ports | 2; 4-pin, D-coded |
| Protocols | PROFINET IO, EtherNet/IP, Modbus TCP |
| Encoder supply outputs | 8 |
| Input delay | 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
| Isochronous mode | 0.25 ms |
| Protection | IP65/67/69K |
| Firmware version | V5.1.x |
| Product lifecycle | Active Product |
Frequently Asked Questions
What is the exact configuration of Siemens 6ES7141-6BH00-0BB0?
It is a SIMATIC ET 200eco PN device with 16 digital inputs, 24 V DC input voltage, M12-L connection, and 8 M12 ports.
Which network interfaces and protocols does it support?
It has 1 PROFINET interface with 2 M12, 4-pin, D-coded ports and supports PROFINET IO, EtherNet/IP, and Modbus TCP.
What supply voltage does this device require?
Load voltage 1L+ is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
What diagnostics are available?
Channel diagnostics include wire break at the input and encoder power supply short-circuit detection. Diagnostic, maintenance, and hardware interrupts are parameterizable.
What quantity and destination should be included for a quotation?
Send the required quantity, destination, and project-list context for model-specific quotation support.