PLC & Distributed I/O Parts

6ES7134-4NB51-0AB0

Product details

Product Code
6ES7134-4NB51-0AB0
Dimensions
8.8 × 6.3 × 2.2 cm
Weight
0.044 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • RTD input capacity: Has 2 analog RTD inputs for 2-/3-/4-wire sensors.
  • Measurement resolution: Resolution with overrange is up to 16 bit including sign; for Pt100, Ni100, Ni120, Pt200, Ni200, Pt500, Ni500, Pt1000, Ni1000 and Cu10 it is 15 bit + sign.
  • Accuracy: Resistance-type transmitter operational error limit is ±0.1%; Pt100, Pt200, Pt500 and Pt1000 standard: ±1.0 K; climate: ±0.25 K.
  • Supply and protection: Rated load voltage L+ is 24 V DC from the power module; reverse polarity protection is provided.
  • Sensor connections: Supports 2-wire, 3-wire with internal compensation of line resistances, and 4-wire resistance measurement.
  • Diagnostics and dimensions: Provides wire-break, group-error and overflow/underflow diagnostics with a red SF group-error LED; width is 15 mm, height 81 mm and depth 52 mm.

Technical Summary

Product type SIMATIC DP ET 200S electronics module, 2AI RTD High Feature
Order number 6ES7134-4NB51-0AB0
Analog inputs 2
Rated load voltage L+ 24 V DC; from power module
Sensor connections 2-wire, 3-wire, 4-wire
Resolution Up to 16 bit including sign; 15 bit + sign for specified RTD types
Operational error limit Resistance-type transmitter: ±0.1%; specified RTD limits vary by standard or climate
Diagnostics Wire break, group error, overflow/underflow
Product lifecycle Product cancellation

Frequently Asked Questions

What is Siemens 6ES7134-4NB51-0AB0?

It is a SIMATIC DP ET 200S electronics module with 2 AI RTD High Feature inputs, 15 mm width, and 2-/3-/4-wire sensor connections.

What supply does the module use?

Its rated load voltage L+ is 24 V DC from the power module, with reverse polarity protection.

Which sensor connections are supported?

It supports 2-wire, 3-wire with internal compensation of line resistances, and 4-wire resistance measurement.

What diagnostics are available?

Wire-break, group-error and overflow/underflow diagnostics are available, with a red SF group-error LED.

How can I request a quotation for this configuration?

Send the required quantity, destination and project-list context for quotation review.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote