Product information
Overview
Applications
- Logic links: Two outputs can be switched in parallel for logic links.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Key Features
- Relay output capacity: 4 parameterizable relay outputs support current-sinking and current-sourcing operation, with up to 2 A per channel and 8 A per module.
- Changeover contacts: The module has 4 changeover contacts with a rated switching voltage of 24 V DC and 24 V AC.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics: It provides supply-voltage monitoring, diagnostic alarms, substitute values, a green PWR LED, and a green/red DIAG LED.
- Installation load limits: For horizontal installation, the maximum module current is 8 A up to 40 °C, 6 A up to 50 °C, and 4 A up to 60 °C. For vertical installation, it is 8 A up to 30 °C, 6 A up to 40 °C, and 4 A up to 50 °C.
- Isolation and mounting: Channels are isolated from each other, the backplane bus, and the electronics power supply. The module fits BU type A0 and has type C mechanical coding.
Technical Summary
| Product type | RQ CO 4x24VDC/2A ST |
|---|---|
| Output type | Relays |
| Number of digital outputs | 4 |
| Current per channel, max. | 2 A |
| Current per module, max. | 8 A |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Rated switching voltage | 24 V DC; 24 V AC |
| Usable BaseUnit | BU type A0 |
| Firmware version | V0.0 |
| PROFINET GSDML | V2.3 |
| PROFIBUS GSD revision | Revision 3 and 5 and higher |
Frequently Asked Questions
What is the exact product type of 6ES7132-6GD51-0BA0?
It is the SIMATIC ET 200SP signal relay module RQ CO 4x 24V DC/2A ST with 4 changeover contacts.
What supply voltage does the module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
What are the output current limits?
The maximum current is 2 A per channel and 8 A per module, subject to the stated installation and temperature limits.
Which BaseUnit fits this module?
The usable BaseUnit is BU type A0.
How can I request a quotation for this configuration?
Send the required quantity, destination, and project-list context for quotation review.